Endress Hauser Digital conductivity sensorMemosens CLS15E-GRHB10B
Field of application
Memosens CLS15E is perfectly suited for conductivity measurement in applications with low measuring ranges such as boiler feedwater and chip cleaning. The contacting conductivity sensor performs reliably and accurately even in hazardous areas. CLS15E features Memosens 2.0 digital technology, offering extended storage of calibration, adjustment and process data. It facilitates predictive maintenance and provides the perfect basis for IIoT services.
Memosens CLS15E measures conductivity in pure and ultrapure water applications for the monitoring and control of:
Boiler feedwater
Ion exchangers
Reverse osmosis
Cooling water
Distillation
Chip cleaning
The digital sensor can be used in power plants for:
Degassed conductivity
pH measurement with differential conductivity
With its international explosion protection approvals, such as ATEX and FM, the sensor is suitable for hazardous area use.
Potentiometric
Measuring principle
Conductive
Application
Measurement in pure and ultrapure water range
Monitoring of ion exchangers
Reverse osmosis
Distillation and chip cleaning
Characteristic
Digital 2-electrode conductivity sensor
Measuring range
k=0,01: 0.04 to 20 µS/cm
k=0,1: 0.10 to 200 µS/cm
Measuring principle
Conductive conductivity cell with electropolished stainless steel electrodes
Design
2-electrode conductivity cell with coaxially arranged electrodes, electropolished
Material
Electrode: stainless steel 1.4435
Electrode shaft: PES
Dimension
Electrode diameter: 16 mm (0.63 inch)
Electrode length: appr. 55 mm (2.17 inch)
Process temperature
Threaded with fixed cable:
-20 to 100 °C (-4 to 212 °F)
Threaded with plug-in head:
-20 to 120 °C (-4 to 248 °F)
Sterilization: max. 140 °C (284 °F) for 30 minutes
Process pressure
13 bar at 20 °C (188 psi at 68 °F) absolute
2 bar at 120 °C (14 psi at 248 °F) absolute
Temperature sensor
Pt1000
Ex certification
ATEX, NEPSI, CSA, IECEx, INMETRO, EAC Ex
Ingress protection
IP68
Additional certifications
Calibration certification of the cell constante and temperature, material certification 3.1
Connection | Process: 1/2" and 3/4" NPT, Clamp 1 1/2" |
Sensor connection: Inductive, digital connection head with Memosens 2.0 technology |