Product No :MTL5561
Input voltage :6 to 30V dc
Current range :1 to 40mA, nominal
Shipping weight :2 Kg
quality guarantee :1 year
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

MTL5561 DIN Rail Isolating IS Interface Unit

The MTL5561 is a loop-powered 2–channel interface for use with conventional fire and smoke detectors located in hazardous areas.

  • Product type : Fire And Smoke Detector Interface

  • Number of channels : Two, fully floating, loop powered

  • Location of fire and smoke detectors : Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A, hazardous area

  • Input voltage : 6 to 30V dc

  • Current range : 1 to 40mA, nominal

  • Quiescent safe–area current at 20°C : (hazardous–area terminals open circuit) < 400µA at Vin = 24V per channel

  • Integral input polarity protection : Input circuit protected against reverse polarity

  • Minimum output voltage Vout at 20°C : For Vin = 25V: Vout = Vin – (0.38 x current in mA) – 2V, For Vin > 25V: Vout = 22.5V – (0.35 x current in mA)

  • Maximum output voltage : 28V from 300?

  • Transfer accuracy at 20°C : Better than 400µA

  • Temperature drift : < 4µA/°C ( 0°C to 60°C), < 15µA/°C (–20°C to 0°C)

  • Response time to step input Settles to within 5% of final value within 1.5ms

  • Power dissipation within unit : 0.7W maximum at 24V with 40mA signal (each channel) 0.9W maximum at 30V with 40mA signal (each channel)

  • Safety description for each channel Uo=28V Io=93mA Po=0.65W Um = 253V rms or dc

  • Shipping weight : 2 Kg

    MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered