Achievers Automation Limited

chievers Automation Limited

Manufacturer from China
Verified Supplier
1 Years
Home / Products / MTL Instruments /

MTL4549 MTL4500 MTL Instruments Intrinsically Safe Isolators

Contact Now
Achievers Automation Limited
Visit Website
City:hong kong
Country/Region:china
Contact Person:MsJoanna Yang
Contact Now

MTL4549 MTL4500 MTL Instruments Intrinsically Safe Isolators

Ask Latest Price
Video Channel
Brand Name :MTL
Model Number :MTL4549
Certification :HART
Place of Origin :UK/China
MOQ :1
Price :Negotiate
Payment Terms :T/T
Supply Ability :1000pcs per week
Delivery Time :stock
Packaging Details :carton
Manufacturer :MTL Instruments
Product No :MTL4549
Working range :4 to 20mA
Digital signal bandwidth :500Hz to 10kHz
Under range capability :1mA
Over range capability :24mA (load ≤ 520Ω)
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

MTL4549 - MTL 4500 Intrinsically Safe Isolators

MTL4549/C/Y - MTL5549/Y ISOLATING DRIVER two-channel, for 4–20mA, HART® valve positioners with line fault detection The MTLx549 accepts 4/20mA floating signals from safe-area controllers to drive 2 current/pressure converters (or any other load up to 800Ω) in a hazardous area. For HART valve positioners, the module also permits bi-directional transmission of digital communication signals. Process controllers with a readback facility can detect open or short circuits in the field wiring: if these occur, the current taken into the terminals drops to a preset level. The MTL4549C and MTLx549Y are very similar to the MTLx549 except that they provide open circuit detection only (i.e. no short-circuit detection).

• Number of channels
Two
• Location of I/P converter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A, hazardous location
• Working range
4 to 20mA
• Digital signal bandwidth
500Hz to 10kHz
• Maximum load resistance
800Ω (16V at 20mA)
• Minimum load resistance
90Ω (short-circuit detection at < 50Ω)
• Output resistance
> 1MΩ
• Under/over range capability
Under range = 1mA
Over range = 24mA (load ≤ 520Ω)
• Input and output circuit ripple
<40µA peak-to-peak
• Communications supported
HART
• Transfer accuracy at 20°C
Better than 20µA
• Temperature drift
< 1.0µA/°C
• Input characteristics
Normal :< 6.0V
Open-circuit: < 0.9mA
Short-circuit :< 0.9mA
• Response time
Settles within 200µA of final value within 100ms
• LED indicator
Green: power indication
• Maximum current consumption (with 20mA signals into 250Ω load)
70mA at 24V dc
• Power dissipation within unit (with 20mA signals into 250Ω load)
1.6W at 24V
• Safety description (each channel)
Uo=28V Io=93mA Po=0.65W Um = 253V rms or dc

MTL4549 MTL4500 MTL Instruments Intrinsically Safe Isolators

HCU16 MTL5521 MTL4575
HCU3700 MTL5522 MTL4646Y
HM64RIB20-1.0 MTL5531 MTL4850
HM64RIB20-1.5 MTL5532 MTL4851
HMM64 MTL5541 MTL4852
HMRIB16-1.0 MTL5541S MTL5018
HMS64 MTL5544 MTL5032
HTP-SC32 MTL5544D MTL5042
MTL4044D MTL5546 MTL5044
MTL4511 MTL5546Y MTL5049
MTL4516 MTL5561 MTL5511
MTL4516C MTL5573 MTL5514D
MTL4521 MTL5575 MTL5516
MTL4541 MTL5582B MTL5516C
MTL4541 MTL7728+ MTL7787P+
MTL4544 MTL7756AC MTLCPS16
MTL4544D MTL7760AC NJ5-18GK-N
MTL4546Y MTL7761PAC SD150X
MTL4549Y MTL7765AC SD32
MTL4573 MTL7787+ SD32X
TP48-4-N-NDI TP48-3-N-NDI SDRTD
TP48-N-NDI TP48-4-I-NDI SLP32D

Inquiry Cart 0