Compact evaluation unit for speed monitoring DI0101 DIA2010-ZROA/5-3600 I/MIN
Reliable non-contact monitoring of the rotational speed with regard to underspeed
2 in 1: speed sensor and evaluation in one compact housing
Easy setting of the switch point via potentiometer
For direct connection to a PLC
Reduced installation complexity
Output function | normally open |
Sensing range[mm] | 10 |
Housing | Threaded type |
Dimensions[mm] | M30 x 1.5 / L = 80 |
Application
Application | simple evaluation of rotating and linear movement with regard to underspeed; blocking |
Electrical data
Nominal voltage AC[V] | 20...250 |
Nominal voltage DC[V] | 20...250 |
Nominal frequency AC[Hz] | 45...65 |
Protection class | II |
Reverse polarity protection | yes |
Outputs
Total number of outputs | 1 |
Output function | normally open |
Max. voltage drop switching output DC[V] | 8.5 |
Minimum load current[mA] | 6 |
Max. leakage current[mA] | 1.5 |
Permanent current rating of switching output AC[mA] | 350 |
Permanent current rating of switching output DC[mA] | 100 |
Short-time current rating of switching output[mA] | 2200; (20 ms / 0,5 Hz) |
Short-circuit proof | no |
Overload protection | no |
Monitoring range
Sensing range[mm] | 10 |
Sensing range adjustable | no |
Real sensing range Sr[mm] | 10 ± 10 % |
Operating distance[mm] | 0...8.1 |
Measuring/setting range
Setting range[Imp/min] | 5...3600 |
Measuring principle | inductive |
Accuracy / deviations
Correction factor | steel: 1 / stainless steel: 0.8 / brass: 0.5 / aluminum: 0.5 / copper: 0.4 |
Hysteresis[% of Sr] | 10 |
Reaction times
Start-up delay[s] | 12 |
Max. damping frequency[Imp/min] | 4800 |
Software / programming
Adjustment of the switch point | multiturn potentiometer |
Operating conditions
Ambient temperature[°C] | -25...80 |
Storage temperature[°C] | -25...80 |
Protection | IP 65; IP 67 |
Tests / approvals
EMC | EN 60947-5-2 |
MTTF[years] | 435 |
Mechanical data
Weight[g] | 281.6 |
Housing | Threaded type |
Mounting | flush mountable |
Dimensions[mm] | M30 x 1.5 / L = 80 |
Thread designation | M30 x 1.5 |
Material | brass special coating; PA; TPE-U |
Tightening torque[Nm] | 50 |
Displays / operating elements
Display | Switching status2 x LED, yellow |
Electrical connection
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
Accessories
Items supplied | lock nuts: 2 |
Remarks
Remarks | Recommendation Check the safe functioning of the unit after a short circuit. |