IFM Evaluation unit with display for PT100/PT1000 temperature sensors TR2439 TR-000KDBM12-MFPKG/US/
Very large temperature evaluation range
Programmable switching output with IO-Link and scalable analog output
Intuitive and user-friendly 3-pushbutton control
Red/green display for clear identification of the acceptable range
Automatic recognition of the connected sensor type
Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 |
Measuring range | -100...600 °C-148...1112 °F |
Communication interface | IO-Link |
Process connection | threaded connection G 1/2 external thread |
Application
System | gold-plated contacts |
Application | for Pt100 and Pt1000 measuring elements |
Electrical data
Operating voltage[V] | 18...32 DC; (cULus - Class 2 source required) |
Current consumption[mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time[s] | 1 |
Integrated watchdog | yes |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 |
Outputs
Total number of outputs | 2 |
Output signal | switching signal; analog signal; IO-Link; (configurable) |
Electrical design | PNP/NPN |
Number of digital outputs | 1 |
Output function | normally open / closed; (configurable) |
Max. voltage drop switching output DC[V] | 2.5 |
Permanent current rating of switching output DC[mA] | 250 |
Number of analog outputs | 1 |
Analog current output[mA] | 4...20 |
Max. load[Ω] | 500 |
Analog voltage output[V] | 0...10 |
Min. load resistance[Ω] | 2000 |
Short-circuit protection | yes |
Type of short-circuit protection | yes (non-latching) |
Overload protection | yes |
Measuring/setting range
Measuring range | -100...600 °C-148...1112 °F |
Factory setting | -40...300 °C / -40...572 °F |
Set point SP | -99.8...600 °C-147.6...1112 °F |
Reset point rP | -100...599.8 °C-148...1111.6 °F |
Analog start point | -100...595 °C-148...1103 °F |
Analog end point | -95...600 °C-139...1112 °F |
In steps of | 0.1 °C0.1 °F |
Accuracy / deviations
Switch point accuracy[K] | ± 0,3 + (± 0,1 % MS) |
Precision analog output[K] | ± 0,3 + (± 0,1 % MS) |
Display accuracy[K] | ± 0,3 + (± 0,1 % MS) |
Temperature coefficient[% of the span / 10 K] | 0,1; (In case of deviation from the reference condition 25 ± 5 °C) |
Reaction times
Response time[ms] | 390 |
Max. response time analog output[ms] | 390 |
Software / programming
Parameter setting options | hysteresis / window; normally open / closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
Interfaces
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |